CO2 Sensor for Duct Mounting
EE85
Duct mounted carbon dioxide transmitters of EE85 series are designed for HVAC applications. The CO2 sensing element uses the Non-Dispersive Infrared Technology (NDIR). A patented auto-calibration procedure compen- sates for drift caused by the aging of the sensing element and guarantees outstanding long term stability.
Installed into a duct a small flow of air will be established by convection through the probe into the transmitter housing and back into the duct. Inside the transmitter housing the air will diffuse through a membrane into the CO2 sensing element.
The operation in closed loop air stream avoids pollution of the CO2 sensor.
Installed into a duct a small flow of air will be established by convection through the probe into the transmitter housing and back into the duct. Inside the transmitter housing the air will diffuse through a membrane into the CO2 sensing element.
The operation in closed loop air stream avoids pollution of the CO2 sensor.
| Technical data | |
| Measuring range: | 0...2000 / 5000 / 10000ppm |
| Outputs: | 0-5 / 10V 4...20mA |
| Accuracy: | 0...2000ppm: < ± (50ppm +2% of measuring value) 0...5000ppm: < ± (50ppm +3% of measuring value) 0...10000ppm: < ± 100ppm +5% of measuring value) |
| Supply: | 24V AC/DC |
The instrument can be easily positioned in the duct with the standard mounting flange
Product inquiry
- Datasheet (278 KB)

- Manual (205 KB)

- Functional principle (68 KB)
- Connecting diagramm (81 KB)
- Case dimensions (79 KB)