Condensation Monitor for Chilled Ceilings
EE46 Serie
EE46 condensation monitors are used to monitor the formation of condensation on chilled ceilings and to prevent condensation at critical spots of heating-, ventilation- and air conditioning systems. It is also used as a dewpoint monitor for systems operating near the dewpoint.
Because of the temperature coupling between the condensation monitor and the environment, the relative humidity is a measure for the dew-point.
The condensation monitor measures the relative humidity near the dewpoint using its high-quality capacitive RH sensor. At reaching the switching point of 90% RH the output will provide an early warning signal for the initiation of control steps (increasing the initial water temperature, reducing the cooling capacity, switching on the heating, etc...).
| Technical data | EE46 |
| Working range: | 10...100% RH |
| Switching point: | 90 +/-3% RH |
| max. switching limits: | current: 1A voltage: 24V AC/DC |
| Supply: | 24V AC/DC |
A special coating protects electronics and sensor against contamination.
The EE46 series can be mounted on pipes, ducts and walls.