An integrated auto-calibration procedure leads to accuracy of ±2 °C (±3.6 °F) Td. The measured values for dew point, frost point or ppm volume concentration are available on an analog 4-20 mA and a digital Modbus RTU output. Integration into the measurement task is simplified by the compact design and the exceptionally robust stainless steel enclosure.
With an optional Modbus to USB convertor and the free EE-PCS configuration software the user can adjust the dew point transmitter, set the Modbus parameters, and change the scaling of the analogue output.
You want to know more about our products?
We are looking forward to help you.
-60...60°C (-76...140 °F) Td
Measuring range±2 °C (±3.6 °F)
AccuracyModbus RTU and 4-20mA
Outputs18-28 V DC
SupplyYou want to know more about our products?
We are looking forward to help you.
Datasheet | |
---|---|
EE355 Datasheet(1301.35 kb) |
|
Scaling of the outputs(252.78 kb) |
|
Accessories(4231.46 kb) |
Manual | |
---|---|
EE355 Manual(818.97 kb) |
|
EE355 Quick Guide(921.81 kb) |
|
Cleaning Instructions(891.89 kb) |
Support literature | |
---|---|
Modbus Application Note AN0103(181.41 kb) |
Software | |
---|---|
EE-PCS Product Configuration Software(29791.22 kb) |
The main difference is the hardware interface. The Modbus RTU protocol runs on RS485 Hardware while Modbus TCP/IP protocol on Ethernet hardware.
The dew point temperature (Td) indicates where condensation begins. The frost point temperature (Td) indicates where icing begins.
Yes, the probe and the sensing element of all E+E dew point measurement devices is wettable.
Low dew point means the difference between the ambient temperature and the dew point temperature is higher than 40 °C (72 °F). This corresponds to RH < 5%.
The appropriate products are the EE371 and EE355. Both devices feature an auto-calibration procedure.
The auto-calibration corrects periodically even the smallest drift of the capacitive sensor at very low relative humidity. This is neccessary for high accuracy and long term stability of the dew point measurement. The auto-calibration is performed every 30 minutes and takes approx. 3 minutes. During the auto-calibration, the output is frozen at the last measured dewpoint value.
Auto-calibration is used by EE371 and EE355.
The standard scope of supply of E+E dew point sensors includes an inspection certificate according DIN EN 10204 - 3.1. For details on calibration certificates please see page 5 in www.kalibrierdienst.at/fileadmin/content/White_Paper_Calibration_and_traceability_in_measuring_technology.pdf
Accredited calibration certificate for CO2 is available upon request, please see our calibration website.
Transmitter with "two-wires" technology receive the power from the process, and the signal is carry on return wire (closed current loop). With technology "three-wires" the power supply is separate from current output: 2 wires are the power supply and third carry the signal.