Condensation Monitor

Link in einer Lightbox öffnen
  • Humidity
  • Dew Point

EE046

The EE046 warns early and reliably of a condensation risk. It thus helps to prevent dripping or mould at critical cold spots. The condensation monitor can be mounted on flat surfaces and on pipes.

  • EE046 humidity and dewpoint condensation monitor for wall/pipe mount

  • EE046 humidity and dewpoint condensation monitor for snap-on mount

    Reliable Condensation Warning
    Condensation on a surface occurs when the relative humidity (RH) of the air close to the surface reaches 100 %. The EE046 condensation monitor measures accurately the relative humidity of the air at the surface temperature. An early warning is given via the relay output when this reaches a value of 90 % RH, just before condensation occurs. The relay also indicates a power supply failure or a broken cable. Additionally, an LED indicates the operating status of the EE046 (normal operation / alarm / power supply failure).

    Mounting on Surfaces and Pipes
    The EE046 condensation monitor is available in two versions. The wall/pipe mount model is appropriate for installation on flat surfaces and on pipes with a diameter of up to 50 mm (2"). It is mounted on cooling ceilings, on cooling or cold water piping, cooled surfaces and chilled beams.

    Snap-On Model for Pipes with 16 mm (0.63") Diameter
    The snap-on model can be mounted on plastic and aluminium composite pipes with 16 mm (0.63") diameter. Typical applications for this model are cooling and heating by concrete core activation.

    Fast Response Time, Long-Term Stable Measurement
    Because of the very good thermal coupling with the surface, the EE046 responds very quickly to humidity or surface temperature changes.

    The high-quality humidity sensing element is protected against dust and dirt by the E+E proprietary coating. This ensures long-term stable and reliable measurements in harsh and polluted environments.

    Typical Applications

    • Concrete core activation
    • Chilled beams
    • Switching cabinets
    • Climate control

    Caratteristiche

    • Fast response time
    • Dust protection
    • Compact design and easy mounting
    • LED status indication

    Dati Tecnici

    Working range
    10...100% RH
    Switching point
    90 ±3% RH
    Response time at change of the surface temperature
    t90 < 3 min.
    Response time at change of the relative humidity
    t90 < 25 sec.
    Max. switch load
    24 V AC/DC, 1 A
    Supply
    24 V AC/DC

    Calibrating your limits

    I vostri prodotti e servizi possono essere precisi solo quanto gli strumenti che utilizzate per misurarli. Con oltre 20 anni di esperienza, il team di calibrazione di E+E Elektronik si concentra sulla fornitura di un servizio affidabile senza inutili ritardi o imprecisioni.

    Scoprite il vantaggio di affidarvi ad un esperto di taratura che dà priorità a

    • accuratezza,
    • rapidità  
    • affidabilità

    Per saperne di più

    Downloads EE046

    Scheda tecnica
    Planning Data

    Vuoi sapere di più sui nostri prodotti?

    Errore: Impossibile caricare il modulo di contatto
    LinkedIn Logo