    EE660 employs E+E air flow sensors manufactured in thin film technology, which stands for excellent accuracy and long-term stability down to 0.15 m/s (30 ft/min). The device is available with current and voltage output or with RS485 interface and Modbus RTU.  EE660 is user configurable and adjustable with jumpers on the electronics board or with the EE-PCS Product Configuration Software.

    Key Features

    • Accurate measurement down to 0.15 m/s (30 ft/min)
    • Excellent long term stability
    • High resistance to pollution
    • Small angle dependency
    • Large, easily readable display
    • Current and voltage output
    • Modbus RTU
    • User configurable and adjustable

    Technical data

    Measuring range selectable by jumper
    0...1 m/s (0...200 ft/min)
    0...1.5 m/s (0...300 ft/min)
    0...2 m/s (0...400 ft/min)
    Accuracy at 20 °C (68 °F), 45 % RH, 1013 hectopascal
    0.15...1 m/s ±(0.04 m/s + 2 % of mv)
    0.15...1.5 m/s ±(0.05 m/s + 2 % of mv)
    0.15...2 m/s ±(0.06 m/s + 2 % of mv)
    Response time(at constant temperature)
    typ. 4 sec or typ. 1 sec.
    Output analogue - selectable
    0-10 V and 4-20 mA
    Output digital
    Modbus RTU
    Supply
    24 V AC/DC

    Calibrating your limits

    Your products and services can only be as precise as the tools you use to measure them. With more than 20 years of experience, the calibration team of E+E Elektronik focuses on providing a reliable service without any unnecessary delays or bias.

    Discover the value of working with an expert in calibration that prioritizes

    • accuracy,
    • fastness and
    • reliability

    Learn more

    Related products

    EE650 Air flow sensor

    EE650

    Air flow transmitter EE75

    EE75

    Air flow sensor EE576

    EE576

    Downloads EE660

    FAQ

    Transmitter with "two-wire" technology receive the power from the process, and the signal is carried on return wire (closed current loop). With "three-wires" technology the power supply is separate from current output: 2 wires are the power supply and the third carries the signal.

    You want to know more about our products?

    LinkedIn Logo