Humidity and Temperature Probe with Digital Output

EE07
The EE07 digital probe is available in polycarbonate and stainlees steel enclosure and measures accurately humidity and temperature over a wide temperature range.
With the choice of appropriate filter cap EE07 is suitable for a variety of demanding applications. The compact design and M12 connector allow an easy system integration. For meteorology and other outdoor applications, the EE07 can be used with the optional radiation shield.
Probe setup and adjustment can be performed with an optional configuration kit.
With optional feature AF4 EE07 is optimized for very low power consumption, ideal for battery powered measurement devices.
Typical Applications
- Humidifiers and dehumidifiers
- Meteorology
- Building automation
- Artificial snow machines
- Data loggers, handheld meters
- Battery powered measurement devices
Key Features
- Highest measurement accuracy
- Outstanding long term stability
- Wide working temperature range
- Temperature compensation
- Compact and easily interchangeable
- Humidity and temperature adjustable by the user
- Low power version EE07-xxAF4
Technical data
- Measuring range
- 0...100% RH
-40...80 °C (-40...176 °F) - Accuracy
- ±2% RH
±0.1 °C (±0.18 °F) - Outputs
- digital E2 (2-wire)
- Supply
- 3.8 - 5.5V DC
Related products
Downloads EE07
FAQ
Certificate Type 2.1
Declaration of compliance with the order - Statement of compliance with the order.
Certificate Type 2.2
Test report - Statement of compliance with the order, with indication of results of nonspecific inspection.
Certificate Type 3.1
Inspection certificate 3.1 - Statement of compliance with the order, with indication of results of specific inspection.
The maximum cable length depends on the product, clock speed, and pull-up resistor, and can be up to 10m. For detail please see E2 interface for humidity probes/modules.
Transmitter with "two-wire" technology receive the power from the process, and the signal is carried on return wire (closed current loop). With "three-wires" technology the power supply is separate from current output: 2 wires are the power supply and the third carries the signal.
Only one E+E device can be connected to the E2 interface of a controller.