E+E Product Finder
9 Products out of 63
CDS201
Room Sensor for CO₂, Temperature and Relative Humidity
- Measuring range - CO₂ 0...2 000 ppm 0...5 000 ppm
- Accuracy - CO₂ < ±(60 ppm +2 % of measured value) < ±(60 ppm +3 % of measured value)
- Measuring range - Humidity 0...100 % RH, non-condensing
- Accuracy - Humidity ±(2.8 + 0.003 * mv) % RH (at 0...80 % RH) ±4.1 % RH (at >80...100 %RH)
- Measuring range - Temperature -30...+60 °C (-22...+140 °F)
- Accuracy - Temperature ±0.35 °C (±0.63 °F), voltage output / RS485 ±0.7 °C (±1.26 °F), current output
- Output analogue 0-10 V or 4-20 mA
- Output digital RS485 (Modbus RTU)
- Power supply 15-35 V DC or 24 V AC ±20 %
EE820
CO₂ Sensor for Demanding Applications
- Measuring range CO₂ 0...2000 ppm 0...5000 ppm 0...10000 ppm
- Accuracy CO₂ at 25 °C (77 °F) and 1013 mbar (14.7 psi) ± (50ppm + 2% of measuring value) ± (50ppm + 3% of measuring value) ± (100ppm + 5% of measuring value)
- Output analogue 0-10 V or 4-20 mA
- Supply 24V AC/DC
EE850
CO₂ and Temperature Sensor for Duct Mounting
- Measuring range CO₂ 0...2000 ppm 0...10000 ppm
- Accuracy CO₂ - *mv - measured value < ± (50 ppm +2% of mv*) < ± (100 ppm +5% of mv*)
- Measuring range Temperature -20...60 °C (-4...140 °F)
- Accuracy Temperature ±0.3 °C (±0.54 °F)
- Output analogue 0-5 / 10 V or 4-20 mA
- Output digital Modbus RTU
- Supply 24 V AC/DC
EE872
Modular Probe for CO₂, Humidity, Temperature and Ambient Pressure
- Measuring Range CO₂ 0…2000 ppm 0…5000 ppm 0…10000 ppm 0…3 % (30000 ppm) 0…5 % (50000 ppm)
- Accuracy CO₂ - * mv – measured value ± (50 ppm + 2 % mv*) ± (50 ppm + 3 % mv*) ± (100 ppm + 5 % mv*) ± (1.5 % from full scale + 2 % mv*) ± (1.5 % from full scale + 2 % mv*)
- Measuring range Relative Humidity 0…95 % RH (non condensing)
- Accuracy Relative Humidity at 25 °C (77 °C) and 20...80% RH typ. ± 3 % RH
- Measuring range Pressure 700…1100 mbar (10.15...15.95 psi)
- Accuracy Pressure at 25 °C typ. ± 2 mbar
- Measuring range Temperature -40…60 °C (-40...140 °F)
- Accuracy Temperature at 5…60 °C (41…140 °F) typ. ± 0.5 °C (± 0.9 °F)
- Output analogue 0-5V / 10 V and 0/4-20 mA
- Output digital Modbus RTU
- Supply 15-35 VDC (current) 12-30 VDC (voltage / RS485)
EE8915
CO₂ Sensor for Railway Applications
- Measuring range 0...2000 ppm 0...5000 ppm 0...10000 ppm
- Accuracy - *mv - measured value <± (50 ppm +2% of mv) <± (50 ppm +3% of mv) <± (100 ppm +5% of mv)
- Outputs 0-5 / 10V and 0 / 4-20mA
- Supply 10-35 V DC
EE894
Digital Sensor Module for CO₂, Temperature, Humidity and Ambient Pressure
- Measuring range CO₂ 0...2000 ppm 0...5000 ppm 0...10000 ppm
- Accuracy CO₂ at 25 °C (77 °F) and 1013 mbar (14.69 psi) ±(50 ppm +2% of mv) ±(50 ppm +3% of mv) ±(100 ppm +5% of mv)
- Measuring range Relative Humidity 0…95 % RH (non condensing)
- Accuracy Relative Humidity at 25 °C (77 °C) and 20...80% RH typ. ± 3 % RH
- Measuring range Pressure 700…1100 mbar (10.15...15.95 psi)
- Accuracy Pressure at 25 °C (77 °C) and 20...80% RH typ. ± 2 mbar
- Measuring range Temperature -40…60 °C (-40...140 °F)
- Accuracy Temperature at 25 °C (77 °F) typ. ± 0.5 °C (± 0.9 °F)
- Digital interface I²C or E2
- Supply 4.75-7.5V DC
EE895
Miniature Sensor Module for CO₂, Temperature and Ambient Pressure
- Measuring range CO₂ 0...2000 ppm 0...5000 ppm 0...10000 ppm
- Accuracy CO₂ at 25 °C (77 °F) and 1013 mbar (14.69 psi) ±(50 ppm +2% of mv) ±(50 ppm +3% of mv) ±(100 ppm +5% of mv)
- Measuring range Pressure 700…1100 mbar (10.15...15.95 psi)
- Accuracy Pressure at 25 °C (77 °C) typ. ± 2 mbar
- Measuring range Temperature -40…60 °C (-40...140 °F)
- Accuracy Temperature at 25 °C (77 °F) typ. ± 0.5 °C (± 0.9 °F)
- Digital interface I²C or UART
- Supply 3.3 - 5V DC
Omniport 40
Multifunctional Hand-Held Meter
- Power Supply 4x AA rechargeable NiMH batteries
- Connections 2x 5-pin M12 connection
- Internal memory Up to 1 million measuring points
- Environmental Conditions (operation) -5...+50 °C (+23...+122 °F); 0...85 % RH non-condensing
- Dimensions 170 x 78 x 38 mm (6.69 x 3.07 x 1.50")
- Protection rating IP67
Sigma 05
Modular Sensor Platform
- MAX. NUMBER OF SENSINGS PROBES 3
- MAX. NUMBER OF MEASURANDS (* 2 ON THE ANALOGUE OUTPUTS / 3 ON THE DISPLAY) 5
- PROBE INTERFACE RS485
- PROTOCOL Modbus RTU
- ANALOG OUTPUTS 0 - 1 V / 2.5 V / 5 V / 10 V 0 / 4 - 20 mA (3-wire)
- ACCURACY OF ANALOGUE OUTPUTS AT 20 °C (68 °F) (*FS = FULL SCALE) 0.02 % FS for 0 - 10 V and 0 - 20 mA
- PROTECTION RATING IP65 / NEMA 4