CO₂, Temperature and Humidity Room Sensor

EE800
EE800 measures accurately CO₂, temperature (T) and relative humidity (RH) in HVAC applications. Additionally, it calculates the dewpoint temperature (Td).
The E+E dual wavelength NDIR CO₂ sensor compensates for aging effects, is highly insensitive to pollution and offers outstanding long term stability. A multiple point CO₂ and T factory adjustment leads to excellent CO₂ measurement accuracy over the entire T working range.
EE800 with analogue outputs features an optional passive T sensor, while EE800 with digital interface (Modbus RTU or BACnet MS/TP) calculates additional physical quantities: absolute humidity, mixing ratio, enthalpy, frost point temperature and water vapor partial pressure.
Applications
- Demand controlled ventilation
- Heating, ventilation and air conditioning
- Building automation
Key Features
- CO₂, T, RH/Td in one room transmitter
- BACnet, Modbus or analogue outputs
- Auto-calibration for excellent long term stability
- Temperature compensation
- Highly insensitive to pollution
- Snap-on enclosure for easy installation
- Optional display
- Easy user configuration and adjustment
Technical data
- Working range CO₂
- 0...2000 ppm
0...5000 ppm - Accuracy CO₂
- < ±(50ppm + 2% of measuring value)
< ±(50ppm + 3% of measuring value) - Working range Humidity
- 10...90 % RH
- Accuracy Humidity
- ±3 % RH (30...70 % RH)
±5 % (10...90 % RH) - Working range Temperature
- -20...60 °C (-4...140 °F)
- Accuracy Temperature
- ±0.3 °C (±0.54 °F) voltage output
±0.7 °C (±1.26 °F) current output - Working range Dewpoint
- -30...55 °C (-22...131 °F)
- Accuracy Dewpoint
- < ±2 °C (3.6 °F) for /T/ - /Td/ < 25 °C (45 °F)
< ±3 °C (5.4 °F) for /T/ - /Td/ < 30 °C (54 °F) - Output analogue
- 0-10 V or 4-20 mA
- Output digital
- Modbus RTU or BACnet MS/TP
- Supply
- 24 V AC/DC