E+E Product Finder

Filter

63 Products

EE451

Wall Mounted Temperature Sensor

  • Operating temperature -40…70°C (-40…158 °F)
  • Accuracy active output ±0.3 °C (±0.54 °F) ±0.1 °C (±0.18 °F) (TT2 version)
  • Analogue output 0-10 V or 4-20 mA
  • Digital interface RS485 with Modbus RTU
  • Protection class IP65 / NEMA 4X
  • Supply 24 V AC/DC
EE451

EE461/EE462

Cable Temperature Sensor

  • Operating temperature - EE461 -30...105 °C (-22...221 °F)
  • Operating temperature - EE462 - Glass fibre 0...350 °C (32...662 °F)
  • Operating temperature - EE462 - Silicone -60...180 °C (-76...356 °F)
  • Protection class IP67 / NEMA 4
  • Insulation resistance typ. > 100 MΩ at 20 °C (68 °F)
EE461/EE462

EE471

Temperature Sensor with Remote Probe

  • Operating temperature remote probe: -30...105 °C (-22...221 °F) electronics: -30...70 °C (-22...158 °F)
  • Accuracy active output ±0.3 °C (±0.54 °F)
  • Analogue output 0-10 V or 4-20 mA
  • Digital interface RS485 with Modbus RTU
  • Protection class IP65 / NEMA 4X
  • Supply 24 V AC/DC
EE471

EE576

Probe for Very Low Air Velocity

  • Measuring range 0...2m/s (0...400ft/min) 0...1m/s (0...200ft/min)
  • Accuracy 0.2... 1m/s: ±(0.05m/s (10ft/min) +2% of MV) 0,2... 2m/s: ±(0.08m/s (16ft/min) +4% of MV)
  • Outputs 0-5V or 0-10V
  • Supply 10-19V DC or 19-29V DC
EE576

EE600

Differential Pressure Sensor

  • Measuring range I: 0...250 / 500 / 750 / 1000 Pa ±250 / ±500 / ±750 / ±1000 Pa
  • Measuring range II: 0...2500 / 5000 / 7500 / 10000 Pa ±2500 / ±5000 / ±7500 / ±10000 Pa
  • Accuracy - *Full Scale (1000 Pa or 10000 Pa) ±0.5 % FS*
  • Overload limits 0...1000 Pa /±1000 Pa ± 10000 Pa 0...10000 Pa / ±10000 Pa ± 80000 Pa
  • Analog outputs - *selectable with DIP switches *0-5 V or 0-10 V *0-20 mA or 4-20 mA 4-20 mA (2-wire)
  • Digital output Modbus RTU
EE600

EE610

Low Differential Pressure Sensor

  • Measuring range 0...25 / 50 / 75 / 100 Pa
  • Accuracy - *Full Scale ±0.5 Pa = 0.5 % FS*
  • Working range - temperature -20...+60°C (-4...140°F)
  • Feature Auto-zero function
  • Overload limit ± 7000 Pa
  • Analog outputs 0-5V / 0-10 V 0-20mA / 4-20mA
  • Digital interface Modbus RTU
  • Power Supply 15 - 35 V DC or 24 V AC ±20 %
EE610

EE650

Air Velocity Sensor for HVAC Applications

  • Measuring range - user selectable 0...10 m/s (0...2000 ft/min) 0...15 m/s (0...3000 ft/min) 0...20 m/s (0...4000 ft/min)
  • Accuracy at 20 °C (68 °F), 45 % RH, 1013 hectopascal 0.2...10 m/s ±(0.2 m/s + 3 % of mv) 0.2...15 m/s ±(0.2 m/s + 3 % of mv) 0.2...20 m/s ±(0.2 m/s + 3 % of mv)
  • Response time - user selectable typ. 4 sec or typ. 1 sec.
  • Output Analogue 0-10 V and 4-20 mA
  • Output Digital Modbus RTU
  • Supply 24 V AC/DC
EE650

EE660

Low Air Velocity Sensor

  • Measuring range selectable by jumper 0...1 m/s (0...200 ft/min) 0...1.5 m/s (0...300 ft/min) 0...2 m/s (0...400 ft/min)
  • Accuracy at 20 °C (68 °F), 45 % RH, 1013 hectopascal 0.15...1 m/s ±(0.04 m/s + 2 % of mv) 0.15...1.5 m/s ±(0.05 m/s + 2 % of mv) 0.15...2 m/s ±(0.06 m/s + 2 % of mv)
  • Response time(at constant temperature) typ. 4 sec or typ. 1 sec.
  • Output analogue - selectable 0-10 V and 4-20 mA
  • Output digital Modbus RTU
  • Supply 24 V AC/DC
EE660

EE671

HVAC Air Velocity Probe

  • Measuring range 0...5m/s (0...1000ft/min) 0...10m/s (0...2000ft/min) 0...15m/s (0...3000ft/min) 0...20m/s (0...4000ft/min)
  • Accuracy 0.5... 5m/s: ±(0.2m/s (40ft/min) +3% of MV) 1... 10m/s: ±(0.3m/s (60ft/min) +4% of MV) 1... 15m/s: ±(0.35m/s (70ft/min) +5% of MV) 1... 20m/s: ±(0.4m/s (80ft/min) +6% of MV)
  • Outputs 0-1/5/10 V (max. 1 mA) Modbus RTU
  • Supply 10-29V DC SELV
EE671

EE680

Air Velocity and Temperature Sensor for Laminar Flow

  • MEASURING RANGE – AIR VELOCITY 0...2 m/s (0...400 ft/min)
  • ACCURACY – AIR VELOCITY (mv = measured value) 0.1...2 m/s (20...400 ft/min): ± (0.5 % of mv + 0.05 m/s)
  • MEASURING RANGE – TEMPERATURE -20...70 °C (-4...158 °F)
  • ACCURACY – TEMPERATURE ±0.5 °C (±0.9 °F)
  • ANALOG OUTPUTS 0-5 V / 0-10 V or 0-20 mA / 4-20 mA (3-wire)
  • DIGITAL OUTPUT Modbus RTU
EE680

EE741

Inline Flow Sensor for Compressed Air and Gases

  • Measured values standardized volumetric flow, mass flow, standardised flow, temperature, consumption
  • Pipe diameter DN15 / DN20 / DN25 DN32 / DN40 / DN50
  • Measuring range - flow DN15: 0.2 - 76.3 Nm³/h (0.12 - 44.88 SCFM) DN20: 0.4 - 135.6 Nm³/h (0.24 - 79.77 SCFM) DN25: 0.6 - 212 Nm³/h (0.36 - 124.71 SCFM)
  • Measuring range - flow DN32: 0.9 - 347.4 Nm³/h (0.52 - 202.06 SCFM) DN40: 1.4 - 542.8 Nm³/h (0.81 - 315.71 SCFM) DN50: 2.2 - 848.2 Nm³/h (1.22 - 493.35 SCFM)
  • Accuracy - flow (*measured value) ±(3 % of mv* + 0.3% of full scale)
  • Measuring range - temperature -20...60 °C (-4...140 °F)
  • Accuracy - temperature ± 0.7 °C (1.26 °F)
  • Outputs 0/4-20 mA, Pulse, Switch, Modbus RTU, M-Bus or IO-Link
  • Supply 18 - 30 V DC
EE741

EE771

Flow Sensor for Compressed Air and Gases

  • Measured values standardized volumetric flow, mass flow, standardised flow, temperature, consumption
  • Measuring range 0.5 - 200 Nm/s (100…39370 SFPM)
  • Accuracy ±1.5 % of the measured value
  • Pipe diameter DN15 up to DN50 (1/2" - 2")
  • Outputs 0-10 V, 0/4-20 mA, Pulse, Switch, Modbus RTU or M-Bus
  • Supply 18 - 30 V AC/DC
EE771
LinkedIn Logo

Live Chat

This website is using Tidio, a chat platform that connects users with the customer support of E+E Elektronik Ges.m.b.H. We are collecting email addresses/names/phone numbers only with the consent of the users, in order to start the chat. The messages and data exchanged are stored within the Tidio application. For more information, please refer to their Privacy Policy. E+E Elektronik Ges.m.b.H is not making use of these messages or data other than to follow up on users’ registered issues or inquiries. Your personal data will be processed and transmitted in accordance with the General Data Protection Regulation (GDPR).